Permit: T10CM03371

Parcel: 137055330

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM03371

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/28/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SHOWER DRAINAGE WATER PROOF OK
03/22/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/16/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE SEE NOTES FROM 3/11/11 INSPECTION CONTINUING TRAP PRIMERS AND INSULATION REQUIREMENTS, INFORMATION PRESENTED TO THIS INSPECTOR REFERENCES THE 2009 IPC CODE AND SAYS NOTHING ABOUT 1/2" RUBATEX INSULATION MEETING 2006 IECC REQUIREMENTS FOR 1" FIBER GLASS INSULATION. REMOVE WRAP AROUND SHOWER DRAINS AND FLOOR DRAINS AND CREATE A WATER TIGHT SEAL PER HANDOUT FOR SHOWER
03/11/2011 PLUMBING - INTERMEDIATE Partial Approval 1. DWV THROUGH THE ROOF OK. WATER DISTRIBUTION OK, PENDING INSTALL OF ALL VALVES PER APPROVED PLAN, AND INSULATION PER APPROVED PLAN, TO MEET 2006 IECC. REQUIRE MOUTS. NEED TO SEE CLOSET FLANGES AFTER FLOORING, PRIOR TO STOOLS AND WATER SEAL FOR SHOWERS.
03/04/2011 PLUMBING - INTERMEDIATE Not ready for Inspection PROVIDE OF 03005+03015INSPECTION APPROVAL OR TEST.
PROVIDE PROOF OF 03005 AND 03015 INSPECTION APPROVAL OR TEST PER NOTES FROM 2/7/11. PROVIDE PIPE PROTECTION PER 2006 UPC. INSTALL ALL PIPING PER APPROVED PLAN OR PROVIDE REDLINES ON SITE WITH CITY APPROVED PLAN TO FOLLOW.