Permit: T10CM03371

Parcel: 137055330

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T10CM03371

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2011 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
1) CALLED CLEARANCE INTO TEP AT 9 AM-ALSO JOANN COT
2) DO NOT ENERGIZE 800 AMP DISC. SW. PRIOR TO INSP APPROVAL-CONTRACTOR TO LOCK OUT
3) CONTRACTOR PAID $165.00 WITH CHECK #46301 FOR APPOINTED TIME OF INSPECTION
03/28/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) EXISTING FEEDER CONDUIT WAS EXPOSED DURING EXCAVATION WILL NEED TO BE REPAIRED, THIS CONDUIT WAS ALREADY BROKEN BUT NOT REPAIRED BY PREVIOUS CONTRACTOR-WILL NEED TO BE FIXED PER CODE
2) OK U.G. WORK BY THIS CONTRACTOR
02/09/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 10 FLOUR BOXES
OK PVC CONDUITS UNDER SLAB FOR BRANCH CIRCUITS
02/07/2011 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*