Permit: T10CM03360

Parcel: 10706013E

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
02/23/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) PROVIDE ACCESS TO VAV PANEL
2) PROVIDE 48" FROM 1ST TAP TO VAV
01/28/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE 48" FROM V.A.V. TO FIRST BRANCH DUCT TAKE OFF PER DETAIL 101 M2.0
2) ALL CHANGES TO PLANS REQUIRE WRITTEN APPROVAL FROM ENGINEER OF RECORD
3) OK TO INSULATE DUCT PENDING ABOVE MENTIONED APPROVAL