Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T10CM03355
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
03/21/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
03/16/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) GW TO TIE IN OK 2) PIPE INSULATION REQUIRES ADHESIVE AT SEAMS AND JOINTS |
|
03/15/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | 1. INSTALLED PER REDLINES. PROVIDE AN APPROVED PLAN REVISION FOR ALL CHANGES MADE. INSTALL CARRIER AND PIPE INSULATION AS SPECIFIED. OK TO COVER TRS SUBJECT TO APPROVED PLAN AT A LATER DATE. ONE HUNDRED POUND TEST ON DOMESTIC WATER. | |
03/14/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | 4" GW FROM INLET PIPE AT INTERCEPTOR BACK INTO STRUCTURE TO ALL FIXTURES SHOWN THRU ROOF WATER TEST OK WITH TWO INCH STUBBED BACK INTO THE BLDG. FOUR INCH SANITARY FROM FIFTEEN FEET FROM EXTERIOR BACK THROUGH TO ALL FIXTURES WATER TEST THROUGH THE ROOF OK, PENDING REVISED APPROVED PLANS FOR CHANGES TO SIZING, ROUTING, AND LOCATIONS. BASEMENT ROUGH TO BE SEEN WITH INTERCEPTOR DISCHARGE BACK TO SANITARY. | |
02/24/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) MIKE WITH CAYLOR AND RAFAEL WITH MTN. STATES |