Permit: T10CM03349

Parcel: 120052740


Addresses:

968 W IRVINGTON RD


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T10CM03349

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2011 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
08/18/2011 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1) WATER TEST INTERCEPTOR VENT OK
2) NEED TO SEE CONNECTION TO BLDG AND INSTALL OF DUMPSTER DRAIN
08/17/2011 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1) INTERCEPTOR OK 4" GW FROM 5 FROM BLDG INCLUDING DUMPSTER STUB UP WATER TEST OK
2) PROVIDE CORRECT VENT CONNECTION FOR INTERCEPTOR WITH TEST ON VENT PIPING. MINIMUM (COMBO AT 45 DEGREE=VERTICAL)
08/16/2011 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1) 6" SANITARY FROM 5' FROM BLDG WEST SIDE THRU TO POINT OF CONNECTION WATER TEST. 4" SANITARY FROM INTERCEPTOR TO 6" WATER TEST OK
08/15/2011 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
1) PROVIDE MATERIAL SCHEDULE ALLOWING SDR 35 FOR SEWER
2) PROVIDE MATERIAL SCHEDULE ALLOWING SDR 35 FOR GREASE WASTE
3) INTERCEPTOR SET-FILL THE INTERCEPTOR ALL THE WAY UP
4) NO TEST ON GREASE WASTE PIPING, EXPOSE CONNECTION TO SEWER AND WHERE IS INTERCEPTOR VENT ?
5) ALL PIPING SUBJECT TO TEST AND VERIFICATION OF GRADE BY ENGINEER OF RECORD
08/11/2011 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
1) PROVIDE AN APPROVED SITE UTILITY PLAN
2) NON METALLIC UTILITIES REQUIRE TO BE TRACEABLE