Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T10CM03349
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2011 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/20/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VENT FOR INTERCEPTOR INSTALLED OK-OK TO COVER |
|
10/14/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BAR AREA DWV AND WATER OK 2) FOR AIR ADD VALVE AT FINAL |
|
10/08/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) USE 2 HOLE STRAPS ON VERTICAL SUPPORT 2) OK TO COVER WALLS AFTER INSULATION |
|
10/06/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV TEST THRU ROOF OK SUPPORTS, PROTECTION PLATES AS REQUIRED & SUPPORT ALL HORIXONTAL ABS AT 4' INTERVALS ABOVE CEILING 4" VENT AT TRU-4 IS REQUIRED TO BE 10' FROM ANY WATER PIPING TO BE INSTALLED PER PLAN |