Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 09/29/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) INSTALL OF P-TRAP AND VENT WATER TEST OK TO 5' FROM BLDG ON VENT FOR DUMPSTER DRAIN 2) VENT FROM INTERCEPTOR AND VENT FROM DUMPSTER DRAIN AT 5' FROM BLDG WILL REQUIRE RETEST FOR INSIDE BLDG FITTINGS |
|
| 08/22/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | 1. VENTS ADDED TO 1 FLOOR SINK, 1 FLOOR DRAIN PER ROD LINE ON SITE, 2" DRAIN ADDED FOR 3-COMP SINK AT BAR OK FOR AIR ADMITTANCE VALVE THAT LOCATION. SANITARY THROUGH BUILDING WATER TEST 1. ADD DIRECT DRAINAGE CONNECTION FOR 3 COMPARTMENT SINK AT BAR AND PROVIDE VENTS FOR 1 FLOOR DRAIN AND 1 FLOOR SINK SAME AREA ???? COMBO WASTE & VENT SYSTEM INCLUDING HCS. GW THROUGH INTERCEPTOR WATER TEST OK. 2. NEED TO SEE INTERCEPTOR VENT INTO BUILDING & INSTALLATION OF DUMPSTER DRAINAGE WITH VENT. |