Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T10CM03349
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2011 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
11/08/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) UNDERGROUND TO MONUMENT AND FREEWAY SIGN 24" BELOW DRIVE WAY |
|
11/04/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE ON SITE AWARE OF INSPECTION NEEDED |
|
09/20/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK POLE BASE NORTH OF BLDG |
|
09/16/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK SIGN CONDUIT FROM MONUMENT TO ROAD CROSSING |
|
09/12/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CONDUIT TO SHALLOW 2) REINSPECTION FEE NEXT INSPECTION IF NO COMPLIANCE |
|
09/09/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
09/08/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEC 300.5 18" MINIMUM TOP OF CONDUIT TO FINISH GRADE AND ROADWAYS 24" |
|
09/07/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK SECONDARYS CONDUITS 2) NO UFER ? |
|
09/01/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
08/24/2011 | ELECTRIC - UNDERGROUND | Partial Approval | 1. UFER REQUIRED PER NEC 250 2. OK SECONDARY CONDUITS 3. OK BRANCH CIRCUIT IN SLAB |