Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/06/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/01/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABELING TO BE PER 690.17 2) GROUNDING ELECTRODE TO BE PER 250.64 3) CANNOT STACK LUGS 4) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 5) MISSING DEAD FRONT COMBINER PANEL 6) GROUNDING ELECTRODE TO MICRO INVERTER NOT TO CODE OR PLANS 7) GROUND MICRO INVERTERS 8) GROUND PV ARRAYS 9) SEAL ROOF JACK 10) LOOSE FITTINGS 11) SUPPORT ALL PV CONDUCTORS AND GROUNDS (NOT TAPE) 12) VERIFY BOX FILL ON ROOF 13) MAINTAIN WORKING SPACE 110.26 |