Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* M4: 1) INSTALL BREAKERS LISTED FOR USE IN CULTER HAMMER PANEL 2) BACK FED BREAKERS TO BE SECURED IN PLACE 3) NEED PANEL DIRECTORY 4) BLANK OPEN BREAKER POSITIONS IN PANEL 5) RECEPT UNDER PANEL TO HAVE WEATHER PROOF COVER M1: 1) BLANK OPEN BREAKER POSITIONS IN PANEL 2) INSTALL BREAKERS LISTED FOR USE IN CUTLER HAMMER PANEL 3) NEED HANDLE TIE ON 40 AMP ? 4) BACK FED BREAKERS TO BE SECURED IN PLACE 5) SEAL OPEN KNOCKOUTS 6) RECEPT UNDER PANEL TO BE WEATHER PROOF 7) IT APPEARS PANEL IS BEING FED WITH ROMEX THAT MAY BE DIRECT BURY. HAVE ELECTRICAL CONTRACTOR INVESTIGATE 8) NEED PANEL DIRECTORY 9) ELECTRICAL CONTRACTOR TO VERIFY FEEDER TO BLDG SIZE, LOCATION AND ROUTING |
|
| 12/03/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CUSTOMER TO RE-SCHEDULE FOR RICH ON MONDAY |