Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2011 | FIRE - FINAL | Approved | ||
| 01/13/2011 | FIRE - FINAL | Denied | Not approved 1/13/11 1.) All doors that open into the exit pathway must be readily openable without the use of a key. Provide thumb-turn locks for the following doors: (egress side) a.) Pharmacy storage b.) Pharmacy work place c.) Pharmacy prep room 2.) Need cover plates in following area: a.) Pharmacy work place room b.) Pharmacy prep room c.) Next to south door d.) West wall (opening in wall) |