Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2011 | FIRE - FINAL | Approved | PER INSP CARD | |
| 01/31/2011 | FIRE - FINAL | Partial Approval | Temp C of O okay - need to do the following correct sprinkler problems in the following areas: 1. Sprinkler coverage in the dinning area use proper approved NFPA -13 ceiling material. 2. Correct sprinkler coverage on back outside patio no coverage, will need to get approved plans and permit to do this. 3. Need copy of sprinkler inspection report left on site for owner to make copies . |
|
| 01/26/2011 | FIRE - FINAL | Denied | Not approved 1/26/11 1.) Need annual fire sprinkler inspection report. 2.) Need 5 yr. check valve inspection report. 3.) Need Mechanical Hood Final approved 4.) Need Hood Final approval. 5.) Life/safety inspection OK |
|
| 12/20/2010 | FIRE - FINAL | Cancelled | IVRS - RI canceled |