Permit: T10CM03220

Parcel: 117120200


Addresses:

47 N 6TH AV

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
02/08/2011 FIRE - FINAL Approved PER INSP CARD
01/31/2011 FIRE - FINAL Partial Approval Temp C of O okay - need to do the following correct sprinkler problems in the following areas:
1. Sprinkler coverage in the dinning area use proper approved NFPA -13 ceiling material.
2. Correct sprinkler coverage on back outside patio no coverage, will need to get approved plans and permit to do this.
3. Need copy of sprinkler inspection report left on site for owner to make copies .
01/26/2011 FIRE - FINAL Denied Not approved 1/26/11
1.) Need annual fire sprinkler inspection report.
2.) Need 5 yr. check valve inspection report.
3.) Need Mechanical Hood Final approved
4.) Need Hood Final approval.
5.) Life/safety inspection OK
12/20/2010 FIRE - FINAL Cancelled IVRS - RI canceled