Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/16/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL ROOF JACK AT MAST PENETRATION 2) SERVICE CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP SERVICE 3) GROUND RODS TO BE MINIMUM 6' APART 4) SEAL OPENING AT CABLE ENTRY BACK OF PANEL 5) PER GAS COMPANY REQUIREMENTS ALL ELECTRICAL DEVICES TO BE MINIMUM 36" FROM REGULATOR VENT |