Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM03166
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRE AND GROUND ON WEST SIDE OF HOUSE TO BE PROTECTED FROM PHYSICAL DAMAGE |
|
03/17/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
03/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE TO BE STRAPPED TO WALL 2) ON ROOF PANEL WIRES TO BE IN RACEWAY TO J-BOX NOT ON ROOF OR SHOW ME WIRE INSULATION FOR SUN LIGHT RESISTANT 3 IN ATTIC 3/4 EMT 1ST STRAP FROM ROOF J-BOX LOOSE AND STRAP PIPE 3' FROM BOX 10' AFTER THAT, STRAP LOW VOLTAGE AS WELL 4) GROUND BAR IN DISCONNECT TO BE MACHINE THREADED SCREW NOT SHEET METAL |