Permit: T10CM03166

Parcel: 141301720

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM03166

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/22/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIRE AND GROUND ON WEST SIDE OF HOUSE TO BE PROTECTED FROM PHYSICAL DAMAGE
03/17/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/07/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE TO BE STRAPPED TO WALL
2) ON ROOF PANEL WIRES TO BE IN RACEWAY TO J-BOX NOT ON ROOF OR SHOW ME WIRE INSULATION FOR SUN LIGHT RESISTANT
3 IN ATTIC 3/4 EMT 1ST STRAP FROM ROOF J-BOX LOOSE AND STRAP PIPE 3' FROM BOX 10' AFTER THAT, STRAP LOW VOLTAGE AS WELL
4) GROUND BAR IN DISCONNECT TO BE MACHINE THREADED SCREW NOT SHEET METAL