Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T10CM03166
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/07/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE TO BE STRAPPED TO WALL 2) ON ROOF PANEL WIRES TO BE IN RACEWAY TO J-BOX NOT ON ROOF OR SHOW ME WIRE INSULATION FOR SUN LIGHT RESISTANT 3) IN ATTIC 3/4 EMT FIRST STRAP FROM ROOF J-BOX LOOSE STRAP PIPE 3' FROM BOX 10' AFTER THAT, STRAP LOW VOLTAGE TO 4) GROUND BAR IN DISCONNECT TO BE MACHINE THREADED SCREW NOT SHEET METAL |