Permit: T10CM03166

Parcel: 141301720

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T10CM03166

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2011 BUILDING - FINAL Approved IVRS - Inspection :*
03/07/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE TO BE STRAPPED TO WALL
2) ON ROOF PANEL WIRES TO BE IN RACEWAY TO J-BOX NOT ON ROOF OR SHOW ME WIRE INSULATION FOR SUN LIGHT RESISTANT
3) IN ATTIC 3/4 EMT FIRST STRAP FROM ROOF J-BOX LOOSE STRAP PIPE 3' FROM BOX 10' AFTER THAT, STRAP LOW VOLTAGE TO
4) GROUND BAR IN DISCONNECT TO BE MACHINE THREADED SCREW NOT SHEET METAL