Permit: T10CM03163

Parcel: 121061520


Addresses:

1510 N MCKINLEY AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/08/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
11/16/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE ANGLE IRON STAND MUST SPAN THE ROOF JOISTS. PROVIDE A FULL LENGTH SLEEPER AT LOWER END OF STAND
2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. TERMINATE TO WITHIN 6" OF THE GROUND, USE AN ELBOW AND NIPPLE AT TERMINATION. SUPPORT PVC EVERY 4' AND PROVIDE A ROOF JACK IF PENETRATING THE ROOF
3) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF
4) 50 AMP BREAKER EXCEEDS MAX. ALLOWED. 35 AMP IS MAX, BREAKER SIZE.25 AMP IS MINIMUM