Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 11/16/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE ANGLE IRON STAND MUST SPAN THE ROOF JOISTS. PROVIDE A FULL LENGTH SLEEPER AT LOWER END OF STAND 2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. TERMINATE TO WITHIN 6" OF THE GROUND, USE AN ELBOW AND NIPPLE AT TERMINATION. SUPPORT PVC EVERY 4' AND PROVIDE A ROOF JACK IF PENETRATING THE ROOF 3) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF 4) 50 AMP BREAKER EXCEEDS MAX. ALLOWED. 35 AMP IS MAX, BREAKER SIZE.25 AMP IS MINIMUM |