Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/28/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3/4 PIPE FROM METER TO INVERTER NOT BENT CORRECTLY OR STRAPPED 2) INVERTER AND DISCONNECT TO BE ANCHORED 3) GROUNDING ELECTRODE TO BE LANDED IN DC DISCONNECT NOT IN INVERTER 4) SECOND STRING FIRST AND LAST PANEL ON EAST SIDE MISSING ANCHORS TO RAIL 5) SECOND AND THIRD STRING STANDS MISSING BOOT COVERS 6) ON ROOF FIRST J-BOX BOTH PIPE CONNECTORS LOOSE, TIGHTEN AND CHECK REST OF PIPES AND PANELS |