Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/19/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE MINIMUM 1" MINIMUM CLEARANCE FROM B-VENT TO COMBUSTIBLES
2) ALL REF. LINES INSULATED ON EXTERIOR ARE TO BE COATED TO PROTECT FROM U.V. BREAKDOWN
3) CONDENSATE CANNOT TERMINATE AT WASTE VENT, TERMINATE AT AN APPROVED LOCATION