Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE MINIMUM 1" MINIMUM CLEARANCE FROM B-VENT TO COMBUSTIBLES 2) ALL REF. LINES INSULATED ON EXTERIOR ARE TO BE COATED TO PROTECT FROM U.V. BREAKDOWN 3) CONDENSATE CANNOT TERMINATE AT WASTE VENT, TERMINATE AT AN APPROVED LOCATION |