Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE APPROVED STRUCTURAL ENGINEERS ROOF PLAN FOR UNIT SUPPORT |
|
| 01/19/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ITEMS 2, 3 & 4 DATED 1/13/11 HAVE BEEN CORRECTED 2) ITEMS 1 & 5 NOT READY |
|
| 01/13/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE REDUCINT WASHER WHERE ELECTRIC CONDUIT CONNECTS TO DISCONNECT ON ROOF 2) PROVIDE R8 FLEX DUCT IN THE ATTIC 3) INSULATE ALL BARE SHEETMETAL FITTINGS IN ATTIC 4) DO NOT HAVE ANY SMASHED OR KINKED FLEX DUCT IN ATTIC 5) PROVIDE THE REQUIRED ROOF TOP DRAWING FOR NEW A/C UNIT ON ROOF |