Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10CM03114
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2011 | FIRE - FINAL | Approved | Approved 2/2/11 | |
01/31/2011 | FIRE - FINAL | Partial Approval | 1. Temp C of O okay- still need to work on the following: Hood is approved as is, one fryer and one gas convection oven under hood. Need to change gas line piping; changed by installing elbow to piping and removing the tee next to oven so no gas appliance can be installed outside of hood coverage. Okay to have electrical oven outside of hood no gas 2. Also need to revise plans showing changes to appliance line up and that convection oven outside of hood is electrical only. |
|
01/27/2011 | FIRE - FINAL | Not ready for Inspection | Not ready for inspection 1/27/10 Needs hood final approval |
|
01/19/2011 | FIRE - FINAL | Not ready for Inspection | Not ready for inspection 1/19/11 1.) Need plans and permit for installatin of new hood system |