Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/13/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/10/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL OK EXCEPT AT 3 COMP SINK
11/16/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) YOU HAVE A OFF SET MADE WITH 4 1/8" BENDS TOTALING 180 DEGREE CHANGE OF DIRECTION
2) ELIMINATE 2 1/8" BENDS TO SATISFY UPC 707.5 (YOU DO NOT NEED A FCO FOR MS)
3) PROVIDE 1/4" PER SLOPE; 708
4) ALSO NOTE SECTION 1014.2.1 FOR FLOW CONTROL VENTING, IF NOT USING AN INTERCEPTOR WITH AN INTERNAL FLOW CONTROL
5) RED LINE ANY CHANGES TO YOUR PLAN