Permit: T10CM03097

Parcel: 110113620

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T10CM03097

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/03/2010 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
12/02/2010 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) SPA SHALL BE LISTED AS COUPLING WITH ANSI ALL 2.19.7M
2) HOT WATER SHALL BE LIMITED TO 120 DEGREE AS REQUIRED PER 414.5
3) RPS REQ A CLEARANCE OF 12" TO BOTTOM 603.3.4
4) DRAINS REQUIRE ALSO CERTIFICATION OF EACH BACKFLOW ASSEM. PROVIDE SUPPORT. SECURE SINK. SUPPORT EXP TANK. GRATES REQ ON FS. AIR GAPS REQ.
5) HAMMER ARRESTORS AT LAUNDRY 609.10
6) CLEANOUT PLUGS SHALL BE LISTED TO RECEIVE THE SCREW
11/23/2010 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) ISOLATE COPPER FROM METAL
2) NEED TO INSPECT VENT TERMINATIONS FOR CLEARANCE FROM AIR INTAKES, PROVIDE ROOF ACCESS
11/18/2010 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*