Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM03090
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED OPENINGS IN BOXES AFTER REMOVAL OF NM CABLES 2) JUNCTION BOX NORTH WALL WILL NEED TO BE ACCESSIBLE AFTER DRY WALL 3) OK WALL AND HARD LID AFTER CORRECTIONS |
|
11/12/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) AREA MARED "ASBESTOS"-PLEASE PROVIDE PAPERWORK FOR CLEAN UP OR PERSONS QUALIFIED TO ENTER AREA |
|
11/08/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE PREVIOUS WRITE UP FOR VDV CABLING AND NM CABLES 2) JUNCTION BOXES NOT GROUNDED 3) CUT AND EXPOSD NM CABLE OUT OF BOX 4) BOXES TO BE ACCESSIBLE |
|
11/05/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE DRYWALL FROM CEILING AND WALLS TO INSPECT ELECTRIC, NEED TO SEE WIRING AND CONNECTIONS-FIXTURES CANNOT BE NM CONNECTED 2) SUPPORT VDV CABLING 725.3,8 & 24 AND 800.3 & 24 |