Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T10CM03085
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2011 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
01/07/2011 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) NO LOADS CONNECTED YET 2) NOTE: UFER IS 2 GROUND RODS #4 BARE IN LIEU OF 2/0 AS CALLED ON PLANS-PROVIDE LETTTER FROM ENGINEER OF RECORD FOR APPROVAL OF #4 3) NEED APPROVAL FOR USE OF MC CABLE IN WALLS 4) OK WALLS ROUGH SUBJECT TO APPROVAL FOR MC AND HARD LIDS ALSO |