Permit: T10CM03085

Parcel: 125090140


Addresses:

2627 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T10CM03085

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
04/06/2011 ELECTRIC - UFER Approved IVRS - Inspection :*
01/07/2011 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) NO LOADS CONNECTED YET
2) NOTE: UFER IS 2 GROUND RODS #4 BARE IN LIEU OF 2/0 AS CALLED ON PLANS-PROVIDE LETTTER FROM ENGINEER OF RECORD FOR APPROVAL OF #4
3) NEED APPROVAL FOR USE OF MC CABLE IN WALLS
4) OK WALLS ROUGH SUBJECT TO APPROVAL FOR MC AND HARD LIDS ALSO