Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/30/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/28/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL RE-VENTING SHALL BE DONE 6" ABOVE UPPER FIXTURE
2) 2" TRAP ARMS ARE LIMITED TO 90 DEGREE CHANGE OF DIRECTION
3) P-10 IS INDIRECTLY WASTED, NO DIRECT CONNECTION ALLOWED
4) PREP SINK IS INDIRECTLY WASTED
5) WHY IS A DRAIN CONNECTION INSTALLED
6) OK TO INSULATE HW PIPING