Permit: T10CM03062

Parcel: 13323093C


Addresses:

7700 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
03/22/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/21/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
03/10/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection PLAN SPECS T/L COPPER, PEX MAY NOT BE USED ON RECURCILATED SYSTEMS WITH TEMP ABOVE 140 DEGREES, PLAN SPECS 1" INSULATION
03/08/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection PROVIDE A CITY APPROVED PLAN INCLUDING MATERIAL TYPES AND SIZES, HAVE G-2 CHANGED TO A-2. PROVIDE REQUIRED BURIAL DEPTH OF TUBING, NON METALIC PIPE REQUIRES A TRACER WIRE, ALL JOINTS REQUIRE A TEST. INSTALL PIPE INSULATION AS REQUIRED BY MANUFACTURE INSTALLATION INSTRUCTIONS.