Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/22/2011 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :* |
| 03/21/2011 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection :* |
| 03/10/2011 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
PLAN SPECS T/L COPPER, PEX MAY NOT BE USED ON RECURCILATED SYSTEMS WITH TEMP ABOVE 140 DEGREES, PLAN SPECS 1" INSULATION |
| 03/08/2011 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
PROVIDE A CITY APPROVED PLAN INCLUDING MATERIAL TYPES AND SIZES, HAVE G-2 CHANGED TO A-2. PROVIDE REQUIRED BURIAL DEPTH OF TUBING, NON METALIC PIPE REQUIRES A TRACER WIRE, ALL JOINTS REQUIRE A TEST. INSTALL PIPE INSULATION AS REQUIRED BY MANUFACTURE INSTALLATION INSTRUCTIONS. |