Permit: T10CM03061

Parcel: 11705033A


Addresses:

340 E 6TH ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/11/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/10/2011 PLUMBING - INTERMEDIATE Not ready for Inspection 1. PROVIDE A MINIMUM OF FOUR INCHES CLEARANCE IN FRONT OF VALVES. 2. ALL WATER SUPPLIED EQUIPMENT (BACKFLOW PREVENTORS) REQUIRE A UNION FOR SERVICING. iNDIRECT WASTE PIPE OVER TWO FEET HORIZONTALLY REQUIRES TRAPS. IPC 802.2. PROVIDE PROPER CLEANOUT COVER ON FLOOR CLEANOUT. BEVERAGE EQUIPMENT NOT YET INSTALLED.
01/27/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNDER FLOOR INSTALLED PER APPROVED PLAN