Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM03061
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/07/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. VDV CABLEING TO BE AS PER 725.3 + 24, 800.3 + 24, 300.11 2. OPEN CEILING FOR INSPECTION UNECESSARY INSPECTIONS MAY RESULT IN A REFER |
|
02/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROTECT UDV CAB. FROM SHARP METAL EDGES OK NORTH BAR IN WALL |
|
01/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CORRECTIONS FROM 1/27/11 |
|
01/27/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 725.24 FOR LV CABLING WILL APPLY-BELOW FLOOR AND ABOVE CEILING 2) NOTE: 400.7 + 8 FOR CORDS ABOVE CEILING WILL APPLY 3) PROTECT FEEDER FLEX CONDUIT 4) FILL UNUSED OPENINGS IN PANEL 5) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF PANEL 6) EXPOSED THHN CONDUCTORS IN WALL IS AN UNSAFE CONDITION |