Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2011 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 06/10/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) NEED BUSHING OR BELL END ON RISER 352.46 2) TERMINATE GROUNDING CONDUCTORS |
|
| 05/11/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK DIRECT BURIAL FROM RAMADA TO PEDESTAL 2) BOND BLDG STEEL TO UFER |
|
| 05/04/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK SECONDARY CONDUITS-ALSO OKANITE KOATED MC IS RATED FOR DIRECT BURRIA-OK BUT MUST BWE 24" MINIMUM DEPTH |
|
| 05/03/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK SECONDARY CONDUIT, BE ADVISED, EXPOSED PVC NEEDS TO BE SCH.80 PER COT CODE AMENDMENTS | |
| 04/20/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK PVC FOR BAND SHELL OUTLETS |