Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) OK PER CONVERSATIONS WITH LEE RAY AND MIKE HENSON |
|
| 12/15/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 (E) 2) LABELING ON ALL EQUIPMENT TO BE PER 690.17 3) OPEN INVERTER DISCONNECT 4) NO MORE THAN 300 DEGREE IN CONDUIT RUN 5) VERIFY SUPPORT FO MOUNTING LEG OF ARRAYS |