Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM03023
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
11/02/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE NOT PROPERLY TERMINATED 2) PROVIDE PROPER CLEARANCE 36" TO FACE OF DISCONNECT 3) TIGHTEN ELECTRICAL FITTINGS 4) W/H FLUE PIPE IS TO BE 10' AWAY OR 3' ABOVE COOLER INLET |