Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2012 | ELECTRIC - FINAL | Denied | 1) SYSTEM GROUNDING AT SERVICE DISCONNECT TO COMPLY WITH 250.24 (1). NEC. 2) INSTALL INS. BUSHING 2 1/2" CONNECTOR AT ANT. BLD, 300-4 NEC. 3) NEUTRAL TO BE BONDED AT SERVICE MANI DISC. SW. ONLY PEC 250 NEC. NO MSG. NO PERSONAL ON SITE, COULD NOT LOCATE PLANS/PERMIT |