Permit: T10CM02998

Parcel: 11105026F

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
04/18/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
04/14/2011 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/28/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT ALL FLOW DUCT OFF OF GRID, LIGHTS, PIPES
2) SEAL ALL DUCT JOINTS
3) SUPPORT ALL CEILING DIFFUSERS
4) PROVIDE BACKING AROUND CEILING BOXES IN HARD LIDS
5) PROVIDE CONDENSATE DRAINS PER PLANS
6) REVISE ELECTRIC PLAN IF USING SINGLE PHASE FOR A/C UNITS INSTEAD OF 3 PHASE
7) PROVIDE DUCT SMOKE DETECTORS PER PLANS