Permit: T10CM02998

Parcel: 11105026F

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/09/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*CORRECTIONS OK, STOI AREA OK, CHECK FLOOR SCHUDULE IN RESTROOMS, CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISH FLOOR, OK TO INSULATE
02/03/2011 PLUMBING - INTERMEDIATE Denied df req 2" co. venting not sized per plan and requires addiyional supports. cap screw hole in 4" pipe. safety plates.
water not sized per plan