Permit: T10CM02998

Parcel: 11105026F

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/13/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/06/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/04/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/29/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) ATTACH FIXTURES SECURELY TO GRID 410.16
2) ELECTRIC SUPPORTED PER 300.11
3) VDV CABLING TO BE PER 725.24, 800.24 AND 300.11
4) BOX OVER FILLED
03/28/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*