Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/08/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) #109 WALL OUTLET MC BROKEN AND NOT STRAPPED, REST OF WALLS IN BLDG OK |
|
| 02/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT VDV CABLEING FROM SHARP METAL EDGES 2. SECURE M/C TO STRUCTURE NOT ITSELF 3. JUNCTION BOXES TO BE ACCESSABLE 4. VDV CABLING TO BE AS PER 725.3 + 24, 800.3+24 5. PLANS CALL FER 3/4" EMT - PLEASE PROVIDE AUTHORIZATION FOR 1/2" + M/C OK WALLS AFTER CORRECTIONS |