Permit: T10CM02998

Parcel: 11105026F

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/13/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/08/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/09/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) #109 WALL OUTLET MC BROKEN AND NOT STRAPPED, REST OF WALLS IN BLDG OK
02/03/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT VDV CABLEING FROM SHARP METAL EDGES
2. SECURE M/C TO STRUCTURE NOT ITSELF
3. JUNCTION BOXES TO BE ACCESSABLE
4. VDV CABLING TO BE AS PER 725.3 + 24, 800.3+24
5. PLANS CALL FER 3/4" EMT - PLEASE PROVIDE AUTHORIZATION FOR 1/2" + M/C

OK WALLS AFTER CORRECTIONS