Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/04/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CANNOT USE SHEET METAL THREAD SCREWS 250.8 2) CLEAN SURFACE UNDER LUGS 250.12 3) GROUND SERVICE DISCONNECT PER 250.12 3) GROUND SERVICE DISONNECT PER 250.24 4) WILL NEED REJECTION PINS 5) FINISH2,3 & 9 |
|
| 11/02/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL UNUSED OPENING IN BOX 2) SUPPORT M/C WITHIN 12" OF CANS, BOXES AND PANEL 3) SUPPORT CONDUITS PER CODE 4) SERVICE ENERGIZED WITHOUT CLEARANCE 5) ONLY ONE CONDUCTOR PER LUG 6) BOND BUSHING NEEDED AT CONCENTRICS 7) #8 AND LARGER CONDUITS TO BE STRANDED IN RACEWAYS 8) DO NOT TIE CONDUCTORS WITH PLASTIC/PAPER 9) MAINTAIN WORKING CLEARANCES |