Permit: T10CM02997

Parcel: 117042780


Addresses:

543 N 4TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM02997

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/04/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CANNOT USE SHEET METAL THREAD SCREWS 250.8
2) CLEAN SURFACE UNDER LUGS 250.12
3) GROUND SERVICE DISCONNECT PER 250.12
3) GROUND SERVICE DISONNECT PER 250.24
4) WILL NEED REJECTION PINS
5) FINISH2,3 & 9
11/02/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FILL UNUSED OPENING IN BOX
2) SUPPORT M/C WITHIN 12" OF CANS, BOXES AND PANEL
3) SUPPORT CONDUITS PER CODE
4) SERVICE ENERGIZED WITHOUT CLEARANCE
5) ONLY ONE CONDUCTOR PER LUG
6) BOND BUSHING NEEDED AT CONCENTRICS
7) #8 AND LARGER CONDUITS TO BE STRANDED IN RACEWAYS
8) DO NOT TIE CONDUCTORS WITH PLASTIC/PAPER
9) MAINTAIN WORKING CLEARANCES