Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM02995
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
11/03/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX DUCT NOT TO EXCEED 8' PER PLANS 2) FLEX DUCT SUPPORTS NOT TO EXCEED 4' PER PLANS 3) FLEX DUCT TAKE OFFS TO BE SPIN-IN, DONE TAILS NOT ALLOWED 4) BRANCH TAPS NOT SEALED 5) DUCT INSULATION TO HAVE BAPOR BARRIER PER I.E.C.C. AND PLANS 6) PROVIDE SEISMIC RESTRAINTS ON ALL REGISTERS 7) ROOF TOP UNITS TO HAVE O.S.A. INLETS 8) PROVIDE FILTERATION FOR O.S.A. |