Permit: T10CM02995

Parcel: 12809006B


Addresses:

5445 E 22ND ST #115


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM02995

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/04/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/03/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLEX DUCT NOT TO EXCEED 8' PER PLANS
2) FLEX DUCT SUPPORTS NOT TO EXCEED 4' PER PLANS
3) FLEX DUCT TAKE OFFS TO BE SPIN-IN, DONE TAILS NOT ALLOWED
4) BRANCH TAPS NOT SEALED
5) DUCT INSULATION TO HAVE BAPOR BARRIER PER I.E.C.C. AND PLANS
6) PROVIDE SEISMIC RESTRAINTS ON ALL REGISTERS
7) ROOF TOP UNITS TO HAVE O.S.A. INLETS
8) PROVIDE FILTERATION FOR O.S.A.