Permit: T10CM02994

Parcel: 118040170

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/29/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) NO BOND REQUIRED
2) DO NOT ENERGIZE INSIDE BRANCH CKTS PRIOR TO APPROVAL
03/24/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) USE APPROVED LISTED GUY SUPPORT FOR RISER CONDUIT AT SERVICE. HOME MADE OUT OF CONDUIT SMASHED ENDS NOT APPROVED
2) WATER AND GAS PIPING BONDING ?
3) MUST HAVE GFI PROTECTED RECEPTS FOR TEMP POWER
03/10/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) USE APPROVED ROMEX CONNECTORS FOR TERM. INTO PANEL
2) PROVIDE LETTER FROM ARCH. OF RECORD FOR USE OF ROMEX CABLE IN LIEU OF CONDUIT AS PER ELECTRICAL NOTES
3) COULD NOT LOCATE SERVICE EQUIP. ON APPROVED PLAN ?