Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/02/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAXIMUM AND MINIMUM 30 AMP FUSE AT COMPRESSOR DISCONNECT AT ROOF (1-30 & 1-25 CURRENTLY IN UNIT) 2) SERVICE OUTLET NEEDED WITHIN 25' OF COMPRESSOR ON ROOF (E.3801.11) |