Permit: T10CM02984

Parcel: 132171270

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/06/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
01/04/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TRANSFORMER GROUND TO GO TO GOLD WATER PIPE NOT SPRINKLER PIPE
2) FILL UNUSED OPENINGS IN FIXTURES
3) PROTECT CONDUCTORS FROM SHARP METAL EDGES
4) GROUND ALL FIXTURES
5) SECURE TRANSFORMER TO FLOOR
6) ONLY ONE CONDUCTOR PER LUG-TWIST SEPERATED ON GROUNDING ON ELECTRODE CONDUCTOR
7) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED TERMINAL