Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 01/04/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TRANSFORMER GROUND TO GO TO GOLD WATER PIPE NOT SPRINKLER PIPE 2) FILL UNUSED OPENINGS IN FIXTURES 3) PROTECT CONDUCTORS FROM SHARP METAL EDGES 4) GROUND ALL FIXTURES 5) SECURE TRANSFORMER TO FLOOR 6) ONLY ONE CONDUCTOR PER LUG-TWIST SEPERATED ON GROUNDING ON ELECTRODE CONDUCTOR 7) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED TERMINAL |