Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2011 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 06/15/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) WATER HEATER FLUE PIPE TO HAVE PRIMER ON ALL JOINTS, PRIMER IS TO BE PURPLE IN COLOR 2) RTU-4 D.S.D. NOT IN APPROVED LOCATION 3) ALL LINE SET INSULATION TO BE COATED FOR U.V, PROTECTION 4) FIRE WRAP NOT COMPLETE 5) NO TESTS HAVE BEEN DONE |
|
| 06/14/2011 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 06/13/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER FIRE WRAP X 3 OK ON GREASE DUCT |
|
| 06/10/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) WELD/LEAK TEST ON GREASE DUCT OK X 3 2) OK FOR 1ST LAYER ENTIRE DUCT |
|
| 06/09/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SMOKE/LEAK TEST ON 3-5' DROPS OK, OK TO 2 LAYER DROPS THRU CURBS 2) PROVIDE MINIMUM 12 X 12 ACCESS DOORS ON TYPE I DUCT OR AS CLOSE AS DUCT SIZE WILL ALLOW |
|
| 06/07/2011 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) PROCEED AS DISCUSSED |