Permit: T10CM02964

Parcel: 11706187D


Addresses:

266 E CONGRESS ST


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10CM02964

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2011 FIRE - FINAL Approved
02/11/2011 FIRE - FINAL Partial Approval Partial approval 2/11/11
1.) Fire Alarm approved (wtrflo/tmpr only)
2.) Need documentation indicating that the curtains have been treated with flame retardant.
02/10/2011 FIRE - FINAL Denied Not approved 2/10/11
1.) Need Fire Alarm Final
a.) Need to replace the smoke detector located over the panel, did not work.
b.) Need to relocate the smoke detector located over the panel. Minimum 36 inches from a regester.
c.) Need to test second phone line.
d.) Water flow and Tamper tested and OK. Good signals recieved
2.) Need Sprinkler Final