Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2010 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/03/2010 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK BATHROOM REGISTER MINIMUM 3 SIDES 2) 8 NAILS NEEDED IN FHA STRAPS FOR MICROWAVE DUCT AT TOP PLATE 3) FHA PLATES NEEDED TOP PLATES OVER 2" VENT 4) INTERIOR BEARING WALL IN KITCHEN NEEDS DBL STUDS TO BORE UP TO 60 PERCENT |