Permit: T10CM02941

Parcel: 13355231B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/26/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/18/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ABOVE CEILING IN OPTICAL OK
05/16/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) INSULATE ALL DUCTING ABOVE OPTICAL
2) SUPPORT ALL CEILING DIFFUSERS
3) OK PARTIAL TILES IN OPTICAL
05/13/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE BEADED COLLARS ON ALL CEILING DIFFUSERS WITH FLEX DUCT CONNECTIONS
2) SUPPORT ALL DIFFUSERS
03/31/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT OK TO PROCEED WITH FLEX + DIFFUSERS. OK PARTIAL TILES IN FITTING ROOM.
OVERHEAD CONDENSATE LINES OK.