Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AIR BALANCE OKAY CONNECT ALL APPLIANCES FOR CAPTURE AND CONTAINMENT EXTEND SEVEN VENTS MIN 2 ABOVE EVAP COOLERS SUPPORT WATER LINES ON ROOF MAX 6' INTERVALS PROVIDE CONNECTORS ON COOLER CORDS |
|
| 08/18/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCT-OK TO DBL WRAP BOTTOM SECTION OF DUCT AND INSTALL, DUCT MUST BE WELDED TO HOOD. HOOD IS EXISTING |
|
| 08/17/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/03/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DISCUSSED ROOF TOP DUCTING AND FANS |
|
| 07/01/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO REUSE HOOD AS TYPE I 2) FAN AND DUCT ON ROOF ARE NOT TYPE I |