Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2011 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 02/14/2011 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED BELL END OR BUSHING 352.46 & 300.4 2) LETTER OF TORQUE NEEDED ON COMPANY LETTER HEAD FOR EQUIPMENT 3) GROUND CONDUCTOR PER 250.24 (C) NEEDED-PLANS CALL FOR 4) BOND METAL RACEWAYS 5) IF EXPOSED TO SUNLIGHT CONDUCTORS TO BE LISTED AND MARKED 310.8 (D) |
|
| 01/07/2011 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) PARTIAL U.G. S.E. EQUIP. PAD 2) GROUND LOOP PARTIAL-TRANSFORMER PAD TO UTILITY POLE GROUND RING AROUND EQUIP PAD NOT IN YET |