Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2010 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 12/10/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH PREVIOUS INSPECTIONS, FAILURE MAY RESULT IN REFEE |
|
| 12/02/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS OR PERMIT ON SITE 2) LABELING NOT PER CODE OR DISCUSSION WITH CONTRACTOR 3) FINISH SUPPORTING CONDUIT 3' FROM FITTINGS 4) FINISH BONDING RAILS AND SUPPORTS 5) INSTALL WEEB LUGS PER MANUFACTURES INSTRUCTIONS |
|
| 11/30/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND GROUNDING ELECTRODE CONDUCTOR TO BE PER 256.64 (E) 2) GROUNDING ELECTRODE TO TERMINATE TO GROUNDED CONDUCTOR 3) PLEASE REVISE PLANS TO MATCH WORK INSTALLED 4) FINISH LABELING PER 690.17 ROOF: 1) SUPPORT RACEWAYS-EMT AND LFNMC 2) BOND RAIL AND SUPPORTS 3) A CONNECTOR FOR NM CABLE IS NEEDED 312.5 |
|
| 11/02/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) MET WITH CONTRACTOR AND ANSWERED QUESTIONS |