Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PHYSICAL PROTECTION FOR #8 GROUNDING ELECTRODE CONDUCTOR 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR AT MARKED TERMINAL IN INVERTER 3) TIGHTEN LOOSE FITTINGS 4) MAINTAIN WORKING CLEARANCES IN FRONT OF A/C DISCONNECT 110.26 5) LABEL MAIN PEDESTAL FOR CODES 690 6) UNCOVER UNDERGROUND TO VERIFY DEPTH PER 300.5 7) ABOVE GRADE PVC TO BE SCHEDULE 80 CITY ADMENDMENTS 8) SUPPORT CONDUIT BELOW A/C DISCONNECT 9) SUPPORT PV CABLES OF OFF ROOF AND PROVIDE PHYSICAL PROTECTION 10) INSTALL WEED LUGS PER MANUFACTURERS INSTRUCTIONS 11) SECURE EQUIPMENT BOND JUMPER TO PROVIDE PHYSICAL PROTECTION 12) JUNCTION BOX NOT ACCESSIBLE 13) NEED UV RATED WIRE TIES |