Permit: T10CM02905

Parcel: 10605150B


Addresses:

521 W SIMMONS RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/21/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PHYSICAL PROTECTION FOR #8 GROUNDING ELECTRODE CONDUCTOR
2) TERMINATE GROUNDING ELECTRODE CONDUCTOR AT MARKED TERMINAL IN INVERTER
3) TIGHTEN LOOSE FITTINGS
4) MAINTAIN WORKING CLEARANCES IN FRONT OF A/C DISCONNECT 110.26
5) LABEL MAIN PEDESTAL FOR CODES 690
6) UNCOVER UNDERGROUND TO VERIFY DEPTH PER 300.5
7) ABOVE GRADE PVC TO BE SCHEDULE 80 CITY ADMENDMENTS
8) SUPPORT CONDUIT BELOW A/C DISCONNECT
9) SUPPORT PV CABLES OF OFF ROOF AND PROVIDE PHYSICAL PROTECTION
10) INSTALL WEED LUGS PER MANUFACTURERS INSTRUCTIONS
11) SECURE EQUIPMENT BOND JUMPER TO PROVIDE PHYSICAL PROTECTION
12) JUNCTION BOX NOT ACCESSIBLE
13) NEED UV RATED WIRE TIES