Permit: T10CM02904

Parcel: 131010500


Addresses:

1300 S ROSEMONT AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/06/2011 FRAMING Approved IVRS - Inspection :*
08/25/2011 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
*STOVE REQUIRES (4) WIRE PULL
*NEED TO SEPARATE CONDUCTORS AT HOME RUNS IN TO MAIN - NO BUILDING OVER 24" ALLOWED
*SEAL HOME RUNS AT MAIN PANEL (REAR)
*NAILS INTO VENT PIPES NEED CORRECTED (LEAKING)
*MOVE ROMEX OFF METAL GUSSETS
07/22/2011 FRAMING Not ready for Inspection IVRS - Inspection :*
07/07/2011 FRAMING Not ready for Inspection IVRS - Inspection :*
04/19/2011 FRAMING Not ready for Inspection IVRS - Inspection :*